Concept:
\(e = {V_{ar}}\left[ {1 - \cos \left( {\frac{t}{{\sqrt {LC} }}} \right)} \right]\)
Var = k1 k2 k3 Em
k1 = sin ϕ
k2 takes into account armature reaction effect.
k3 is phase factor = 1 for both neutral and fault grounded
= 1.5 for any one of the two not grounded.
Em is the peak value of voltage.
Frequency of oscillations.
\({f_n} = \frac{1}{{2\pi \sqrt {LC} }}\)
Average RRRV = (Maximum restriking voltage)/(Time to reach maximum restriking voltage)
Maximum restriking voltage = 2 Var
Time to reach maximum restriking voltage, \({t_m} = \pi \sqrt {LC}\)
Calculation:
Power factor = cos ϕ = 0.4
⇒ ϕ = 66.42°
k1 = sin ϕ = 0.916
Recovery voltage is 0.9 times full line value
⇒ k2 = 0.9
As both neutral and faults are grounded,
k3 = 1
\({E_m} = \frac{{132}}{{\sqrt 3 }} \times \sqrt 2 \;V\)
Maximum restriking voltage
= 2 Var
\(= 2 \times 0.916 \times 0.9 \times 1 \times \frac{{132}}{{\sqrt 3 }} \times \sqrt 2 \times {10^3}\)
= 177.7 kV
Frequency of oscillations, (fn) = 16 kHz
\(\Rightarrow \frac{1}{{2\pi \sqrt {LC} }} = 16 \times {10^3}\)
\(\Rightarrow \pi \sqrt {LC} = 3.125 \times {10^{ - 5}}\) sec = 31.25 μ sec
Average \(RRRV = \frac{{177.7}}{{31.25}} = 5.6864\) kV/μ sec