Self Studies

Power Systems Test 10

Result Self Studies

Power Systems Test 10
  • Score

    -

    out of -
  • Rank

    -

    out of -
TIME Taken - -
Self Studies

SHARING IS CARING

If our Website helped you a little, then kindly spread our voice using Social Networks. Spread our word to your readers, friends, teachers, students & all those close ones who deserve to know what you know now.

Self Studies Self Studies
Weekly Quiz Competition
  • Question 1
    1 / -0
    In a system of 132 kV, the circuit phase to ground capacitance is 0.02 μF, the inductance is 5 H. If a magnetic circuit of 8 A is interrupted instantaneously, the value of the pre-insertion resistor to be used across the contact space is _____ (in kΩ)
    Solution

    Concept:

    The value of the resistance to be used, across the contact space is given by

    \(R = \frac{1}{2}\sqrt {\frac{L}{C}} \)

    Where,

    L is inductance

    C is capacitance

    Calculation:

    Given that inductance (L) = 5 H

    Capacitance (C) = 0.02 μF

    = 0.02 × 10-6 F

    \(R = \frac{1}{2}\sqrt {\frac{5}{{0.02\; \times \;{{10}^{ - 6}}}}} = 7.9\;k{\rm{\Omega }}\)
  • Question 2
    1 / -0
    The rated making current of a circuit breaker is given as 90 kA (peak). The braking capacity (in MVA) of circuit breaker if it is rated at 22 kV
    Solution

    Rated symmetrical braking current \(= \frac{{rated\;making\;current}}{{2.55}} = \frac{{90}}{{2.55}} = 35.29\;kA\)

    Braking capacity \(= \sqrt 3 \times 22 \times 35.29 = 1344.88\;MVA\)
  • Question 3
    1 / -0

    A 10-ampere, over current relay having a current setting of 150% and a time setting multiplier of a 0.8 connected to supply circuit through a 400/5 current transformer when the circuit carries a fault current of 5000 A. Find the plug-setting multiplier.

    Solution

    Rated secondary current of current transformer = 5 A

    Pickup current(Ipickup) = Current setting(A) \(= \frac{{current\;setting\left( \% \right)}}{{100}} \times {I_{relay}}\)

    Current setting(A) = 1.5 × 5 = 7.5 A

    Plug-setting multiplier\( = \frac{{{\rm{Fault\;current}}}}{{{\rm{C.T. ratio\times current\;setting(A)}}}}\)

    \(= \frac{{5000}}{{\frac{{400}}{{5}}\;\times7.5}} = 8.33\)

  • Question 4
    1 / -0
    The short circuit current of a 132 kV system is 8000 A. The current chopping occurs at 2.5% of peak value of current. The value of stray capacitance to the earth is 100 pF. The inductance is 30 mH. The prospective value of the voltage which coil appear across the contacts of the circuit breakers is _______ (in kV)
    Solution

    Concept:

    When low inductive current is being interrupted and the arc quenching force of the circuit breaker is more than necessary to interrupt a low magnitude of current, the current will be interrupted before its natural zero instant.

    In this situation, the energy stored in the magnetic field appears in the form of high voltage across the stray capacitance which will cause restriking of the arc.

    The energy stored in the magnetic field is \(\frac{1}{2}L{i^2}\) where i is the instantaneous value of the current which is interrupted.

    This will appear in the form of electrostatic energy equal to \(\frac{1}{2}C{v^2}\).

    Where V is called the prospective value of the voltage.

    As these two energies are equal, they can be related as

    \(\frac{1}{2}L{i^2} = \frac{1}{2}C{v^2}\)

    \( \Rightarrow v = i\;\sqrt {\frac{L}{C}}\)

    Calculation:

    Given that, short circuit current (If) = 8000 A.

    Current chopping occurs at 2.5% of peak value & current.

    \(i = \frac{{2.5}}{{100}} \times 8000 \times \sqrt 2 = 282.84\;A\)

    Inductance (L) = 30 mH = 30 × 10-3 H

    Stray capacitance (C) = 100 × 10-12 F

    Prospective voltage, \(V = i\sqrt {\frac{L}{C}} \)

    \(= 282.84\;\sqrt {\frac{{30 \times {{10}^{ - 3}}}}{{100 \times {{10}^{ - 12}}}}} \)

    = 4898.98 kV

  • Question 5
    1 / -0

    In short circuit test on a 3 pole, 132 kV circuit breaker, the following observations are made:

    Power factor of fault = 0.4

    Recovery voltage is 0.9 times the full line value.

    The breaking current is symmetrical, frequency of the oscillations of restriking voltage is 16 kHz. If both neutral and fault are grounded, the a value of average RRRV is _______ (in kV/μ sec)

    Solution

    Concept:

    \(e = {V_{ar}}\left[ {1 - \cos \left( {\frac{t}{{\sqrt {LC} }}} \right)} \right]\)

    Var = k1 k2 k3 Em

    k1 = sin ϕ

    k2 takes into account armature reaction effect.

    k3 is phase factor = 1 for both neutral and fault grounded

    = 1.5 for any one of the two not grounded.

    Em is the peak value of voltage.

    Frequency of oscillations.

    \({f_n} = \frac{1}{{2\pi \sqrt {LC} }}\)

    Average RRRV = (Maximum restriking voltage)/(Time to reach maximum restriking voltage)

    Maximum restriking voltage = 2 Var

    Time to reach maximum restriking voltage, \({t_m} = \pi \sqrt {LC}\)

    Calculation:

    Power factor = cos ϕ = 0.4

    ϕ = 66.42°

    k1 = sin ϕ = 0.916

    Recovery voltage is 0.9 times full line value

    k2 = 0.9

    As both neutral and faults are grounded,

    k3 = 1

    \({E_m} = \frac{{132}}{{\sqrt 3 }} \times \sqrt 2 \;V\)

    Maximum restriking voltage

    = 2 Var

    \(= 2 \times 0.916 \times 0.9 \times 1 \times \frac{{132}}{{\sqrt 3 }} \times \sqrt 2 \times {10^3}\)

    = 177.7 kV

    Frequency of oscillations, (fn) = 16 kHz

    \(\Rightarrow \frac{1}{{2\pi \sqrt {LC} }} = 16 \times {10^3}\)

    \(\Rightarrow \pi \sqrt {LC} = 3.125 \times {10^{ - 5}}\) sec = 31.25 μ sec

    Average \(RRRV = \frac{{177.7}}{{31.25}} = 5.6864\) kV/μ sec

  • Question 6
    1 / -0
    In a 132 kV, 50 Hz system, reactance and capacitance up to the location of the circuit breaker is 5 Ω and 0.02 μF respectively. A resistance of 500 Ω is connected across the breaker of the circuit breaker. The damped frequency of oscillation is ______ (in kHz)
    Solution

    Concept:

    The frequency of damped oscillations is given by

    \(f = \frac{1}{{2\pi }}\sqrt {\frac{1}{{LC}} - \frac{1}{{4{C^2}{R^2}}}}\)

    Calculation:

    Given that, inductive reactance (X­L) = 5Ω

    2πfL = 5

    2π × 50 × L = 5

    L = 15.91 mH

    Capacitance (C) = 0.02 μF

    Resistance (R) = 500 Ω

    \(f = \frac{1}{{2\pi }}\sqrt {\frac{1}{{15.91\; \times \;{{10}^{ - 3}}\; \times\; 0.02\; \times \;{{10}^{ - 6}}}} - \frac{1}{{4\; \times\; {{\left( {0.02\; \times \;{{10}^{ - 6}}} \right)}^2}\; \times\; {{\left( {500} \right)}^2}}}} \)

    = 4.03 kHz  

  • Question 7
    1 / -0
    A 3 phase, 15 MVA, 13 kV, star connected alternator is protected by current balancing system of protection. If the ratio of CT is 1500/4, the minimum operating current of the relay is 0.8 A and the neutral point resistance is 4 Ω. The percentage of each phaser of stator winding which is unprotected against faults when the machine is operating at normal voltage is _______ (in %)
    Solution

    Let %x be the stator winding which is unprotected.

    Emf induced in this unprotected winding \( = \frac{{13 \times {{10}^3}}}{{\sqrt 3 }} \times \frac{x}{{100}} = \frac{{130}}{{\sqrt 3 }}x\;V\)

    Fault current, \({I_f} = \frac{{\frac{{130}}{{\sqrt 3 }}x}}{4} = 18.76x\;A\)

    The minimum current which will operate the relay

    \( = \frac{{1500}}{4} \times 0.8 = 300\) 

    Now, 18.76x = 300

    ⇒ x = 15.98%
  • Question 8
    1 / -0
    An 11 kV, 100 MVA alternator is provided with differential protection. The percentage of winding to be protected against phase to ground fault is 85%. The relay is set to operate when there is 20% out of balance current. The value of the resistance (in ohms) to be placed in the neutral to ground connection is
    Solution

    Percentage of winding to be protected = 85%

    Percentage of unprotected winding = 15%

    Voltage (V) = 11 kV

    MVA rating = 100 MVA

    Full load current \(\left( {{I_L}} \right) = \frac{{MVA}}{{\sqrt 3 \times kV}}\)

    \(= \frac{{100 \times {{10}^6}}}{{\sqrt 3 \times 11 \times {{10}^3}}}\)

    = 5248.63 A

    Relay operates when there is 20% out of balance current.

    Minimum fault current (If) = 0.2 × 5248.63

    = 1049.73 A

    Voltage across unprotected winding

    \( = \frac{{0.15 \times 11 \times {{10}^3}}}{{\sqrt 3 }}\)

    = 952.63 V

    Let Rn is the resistance to be placed in the neutral to ground connection.

    \(\Rightarrow 1049.73 = \frac{{952.63}}{{{R_n}}}\)

    ⇒ Rn = 0.907 Ω
Self Studies
User
Question Analysis
  • Correct -

  • Wrong -

  • Skipped -

My Perfomance
  • Score

    -

    out of -
  • Rank

    -

    out of -
Re-Attempt Weekly Quiz Competition
Self Studies Get latest Exam Updates
& Study Material Alerts!
No, Thanks
Self Studies
Click on Allow to receive notifications
Allow Notification
Self Studies
Self Studies Self Studies
To enable notifications follow this 2 steps:
  • First Click on Secure Icon Self Studies
  • Second click on the toggle icon
Allow Notification
Get latest Exam Updates & FREE Study Material Alerts!
Self Studies ×
Open Now