Self Studies

Power Systems Test 11

Result Self Studies

Power Systems Test 11
  • Score

    -

    out of -
  • Rank

    -

    out of -
TIME Taken - -
Self Studies

SHARING IS CARING

If our Website helped you a little, then kindly spread our voice using Social Networks. Spread our word to your readers, friends, teachers, students & all those close ones who deserve to know what you know now.

Self Studies Self Studies
Weekly Quiz Competition
  • Question 1
    1 / -0
    Installation of capacitors at suitable locations and of optimum size in a distribution system results in
    Solution
    Shunt capacitors are used with individual equipment to improve power factor. For fixed power loss and voltage, as power factor increases, current decreases. Therefore, I²R loss decrease. The power losses are reduced and the efficiency is increased. The smaller voltage drop in the line results in good voltage regulation. Thus, shunt capacitors regulate the voltage and reactive power flows at the points where they installed.
  • Question 2
    1 / -0

    A short capacitor used in power system for VAR compensation is operated at 98% of its rated frequency and 95% of its rated voltage. The VAR supplied by shunt capacitor (as compared to its rated capacity) is

    Solution

    Rated line voltage = VLO

    Rated frequency = fo

    3 - ϕ VAR rating

    \(\begin{array}{l}{Q_o} = {\omega _o}CV_{Lo}^2 = 2\pi {f_o}CV_{Lo}^2\\At\ f = 0.98\ {f_o},{V_L} = 0.95{V_{Lo}}\\Q = 2\pi fcV_L^2 = 2\pi \times \left( {0.98{f_o}} \right)C \times {\left( {0.95{V_{L0}}} \right)^2}\end{array}\)

    = 0.885 QO

    \(Percentage\ reduction = \frac{{Q - {Q_o}}}{{{Q_o}}} \times 100\)

    = -11.5%

  • Question 3
    1 / -0
    A 250 MW, 60 Hz turbine generator set has a speed regulation of 5 percent based on its own rating. The generator frequency decreases from 60 Hz to a steady state value of 59.7 Hz. Determine the increase in the turbine power output in MW.
    Solution

    Speed regulation (R) = 0.05

    Change in frequency, Δf = f – f0 = 59.7 – 60 = -0.3 Hz

    \({\rm{\Delta }}f = - \frac{{0.3}}{{60}} = - 0.005\;pu\)

    ΔPm = ΔPL

    \( = - \frac{{{\rm{\Delta }}f}}{R} = 0.1\;pu\)

    ΔPm = 0.1 × 250 = 25 MW
  • Question 4
    1 / -0
    Two generating units rated for 250 MW and 400 MW have their droop settings of 6.0% and 6.4%, respectively. The units operate in parallel at 50 Hz at no load. Determine the load taken by each unit for a total load of 500 MW. Neglect losses and the dependence of load on frequency.
    Solution

    \({\rm{\Delta }}f = \frac{{\% change\;in\;f}}{{{P_{fl}}}} \times {\rm{\Delta }}P\)

    ΔP1 + ΔP2 = 500 MW

    ⇒ ΔP2 = 500 – ΔP1

    Δf1 = Δf2

    \( \Rightarrow \frac{{0.06}}{{250}} \times {\rm{\Delta }}{P_1} = \frac{{0.064}}{{400}} \times {\rm{\Delta }}{P_2}\)

    \( \Rightarrow \frac{{0.06}}{{250}} \times {\rm{\Delta }}{P_1} = \frac{{0.064}}{{400}} \times \left( {500 - {\rm{\Delta }}{P_1}} \right)\)

    ⇒ ΔP1 = 200 MW, ΔP2 = 300 MW
  • Question 5
    1 / -0
    Two generators rated 250 MW and 400 MW are operating in parallel. The droop characteristics of the governors are 4% and 6% respectively.if a load of 450 MW be share between them. What will be the system frequency? Assume nominal system frequency is 60 Hz and no governing action.
    Solution

    Let, Load on generator 1 = x MW

    Load on generator 2 = (450 – x) MW

    Reduction in frequency = Δf

    Now,

    \(\frac{{{\rm{\Delta }}f}}{x} = \frac{{0.04 \times 60}}{{250}}\)      ----(i)

    \(\frac{{{\rm{\Delta }}f}}{{\left( {450 - x} \right)}} = \frac{{0.06 \times 60}}{{400}}\)       ---(ii)

    From equations (i) & (ii), we get

    \(\frac{{450 - x}}{x} = \frac{{0.04 \times 60}}{{250}} \times \frac{{400}}{{0.06 \times 60}} = 1.066\)

    ∴ x = 217.81 MW (load on generator 1)

    450 – x = 232.18 MW (load on generator 2)

    and Δf = 2.09Hz

    ∴ System frequency = (60 – 2.09) = 57.909 Hz.
  • Question 6
    1 / -0

    A 3 – phase overhead line has resistance and reactance per phase of 5 Ω and 20 Ω respectively. The load at the receiving end is 25 MW at 33 kV and a power factor of 0.8 lagging. Find the capacity of the synchronous condenser required for this load condition if it is connected at the receiving end and the line voltages at both ends are maintained at 33 kV.

    Solution

    Load current, \({I_2} = \frac{{25 \times {{10}^6}}}{{\sqrt 3 \times 33 \times {{10}^3} \times 0.8}} = 546.8\ A\)

    \(\begin{array}{l}{I_P} = {I_2}\cos {\phi _2} = 437.4\ A\\{I_q} = {I_2}\sin {\phi _2} = 328.1\ A\end{array}\)

    R = 5 Ω; x = 20 Ω

    Sending end voltage, V1 = receiving end voltage V2

    \(= \frac{{33 \times {{10}^3}}}{{\sqrt 3 }} = 19053\)

    Let Im be the current taken by the synchronous condenser

    \(\begin{array}{l}V_1^2 = {\left[ {{V_2} + {I_P}R - \left( {{I_m} - {I_q}} \right)X} \right]^2} + {\left[ {{I_P}X + \left( {{I_m} - {I_q}} \right)R} \right]^2}\\ \Rightarrow {\left( {19053} \right)^2} = {\left[ {19053 + \left( {437.4} \right)\left( 5 \right) - \left( {{I_m} - 328.1} \right)\left( {20} \right)} \right]^2} + {\left[ {\left( {437.4} \right)\left( {20} \right) + \left( {{I_m} - 328.1} \right)\left( {20} \right)} \right]^2} + {\left[ {\left( {437.4} \right)\left( {20} \right) + \left( {{I_m} - 328.1} \right)\left( 5 \right)} \right]^2}\end{array}\)

    ⇒ Im = 579.5 A

    Capacity of synchronous condenser \(= \frac{{3{V_2}{I_m}}}{{{{10}^6}}}MVAR\)

    = 33.12 MVAR

Self Studies
User
Question Analysis
  • Correct -

  • Wrong -

  • Skipped -

My Perfomance
  • Score

    -

    out of -
  • Rank

    -

    out of -
Re-Attempt Weekly Quiz Competition
Self Studies Get latest Exam Updates
& Study Material Alerts!
No, Thanks
Self Studies
Click on Allow to receive notifications
Allow Notification
Self Studies
Self Studies Self Studies
To enable notifications follow this 2 steps:
  • First Click on Secure Icon Self Studies
  • Second click on the toggle icon
Allow Notification
Get latest Exam Updates & FREE Study Material Alerts!
Self Studies ×
Open Now