Concept:
The fault current in a single line to ground fault is,
\({I_f} = \frac{{3 \times {E_{R1}}}}{{{X_1} + {X_2} + {X_0} + 3{X_n}}}\)
Short-circuit capacity = If × Base MVA
X1 is the positive sequence reactance
X2 is the negative sequence reactance
X0 is the zero-sequence reactance
Xn is the ground reactance
Calculation:
Short circuit capacity = 500 MvA,
Neutral reactance, Xn = 0.05 pu
Zero sequence reactance, X0 = 25% of positive sequence reactance
Base MVA = 100 MVA
3ϕ fault current, \({I_f} = \frac{{{E_{R1}}}}{{X_d^{''}}} \times 100 = \frac{1}{{{X_d}}}pu\)
Short circuit MVA = 500
\( \Rightarrow \frac{1}{{X_d^{''}}} \times 100 = 500\)
\( \Rightarrow X_d^{''} = 0.2\;pu\)
In turbo generator,
Positive sequence reactance, \(X_d^{''}\) = Negative sequence reactance, X2
i.e. \(X_d^{''} = {X_1} = {X_2} = 0.2\;pu\)
Zero sequence reactance, X0 = 25% of \(X_d^{''}\)
= 0.25 × 0.2
= 0.05 pu
For the LG fault,
\({X_{f\left( {LG} \right)}} = \frac{{3 \times {E_{R1}}}}{{{X_1} + {X_2} + {X_0} + 3{X_n}}}\)
\( = \frac{{3 \times 1\;\;}}{{0.2 + 0.2 + 0.05 + 3 \times 0.05}} = 5\;pu\)
Short-circuited capacity for a line to ground fault = If(LG) × Base MVA
= 5 × 100 = 500 MVA